Step 1: which material suits the environment?
PA6 is the workhorse: impact resistant, self-extinguishing and affordable, usable from −40 to +105 °C. PA12 costs more but hardly absorbs moisture, stays flexible at −60 °C and tolerates oil and coolant better. PP is chemically the strongest but mechanically the weakest; use it in wash-down and plating lines, not in a moving run.
Choose metal conduit as soon as heat, sparks or mechanical damage are involved. A galvanised steel wound conduit with PVC jacket is sealed and robust; a stainless version without jacket handles higher temperatures but is not liquid-tight.
Step 2: closed, slit or split profile?
A closed conduit is the only one that achieves an IP rating, but cables must be pulled through. A slit conduit clips around an existing pre-terminated cable — handy for retrofits, but expect IP40 at most. Split hinged conduits sit in between and are splash-proof with a sealing lip.
- Closed: IP66 up to IP69K possible, pull cables in before mounting.
- Slit: retrofit mounting, no sealing claim, ideal for maintenance.
- Split with sealing lip: compromise for dust and splash water.
Step 3: which gland system belongs to it?
Conduit and gland form one system: the gland grips the corrugation of that specific brand. Choose plastic (PA) glands for standard use, nickel-plated brass for vibration and EMC requirements, and stainless for food or outdoor installations. Watch the thread type (metric M or PG) and the enclosure wall thickness.
What changes in a moving application?
On a robot arm or moving run the dynamic bend radius counts, not the static one: allow 1.5 to 2 times the static value. Use swivel glands at the moving end, let the conduit form a generous loop instead of a kink, and place strain relief just behind both glands so the corrugation is not pulled out of the clamp.
| Material | Temperature | Strong at | Avoid with |
|---|---|---|---|
| PA6 | −40…+105 °C | Machinebouw, slagvast | Continu vocht |
| PA12 | −60…+120 °C | Koude, olie, beweging | Budgetprojecten |
| PP | −20…+100 °C | Zuren, logen | Sleepbaan, slag |
| Staal + PVC | −30…+105 °C | Spatten, knaagdieren | Sterk zuur milieu |
| RVS blank | −60…+300 °C | Hitte, vonken | Dichtheidseisen |
Frequently asked questions
- Is PA12 worth the price difference?
- Rarely for fixed indoor installations. Yes for cold, outdoor use, oil or daily movement: PA12 stays flexible and does not crack at low temperature, saving replacement cost and downtime.
- May a conduit run inside a cable carrier?
- Preferably not. A conduit inside a carrier adds friction and volume and stops cables moving freely. Use loose cables with separators inside the carrier and start the conduit at the fixed side.
- Which conduit survives high-pressure cleaning?
- A smooth PA conduit with stainless glands and IP69K approval. Avoid open profile grooves where water and residue collect.
Read next
- What do IP ratings mean for cable protection conduits?The two digits explained, plus why a conduit only achieves an IP rating together with its gland.
- How do you calculate nominal size and conduit length?40% fill ratio, bend radius allowance and installed length: the three formulas with real numbers.
- How do you install a protective conduit without leaks?Cut square, seat to the stop, tighten correctly and clamp: the installation sequence that delivers a seal.