Ships today when ordered before 15:00 CETShips today when ordered before 15:00 CET
Wisman Group

Calculating

Calculating derating at high ambient temperature

Short answerMultiply the base current rating by the temperature factor kT and the grouping factor kB: I_allowed = I_base × kT × kB. If the required current exceeds that, choose a larger conductor size, a cable with a higher temperature class (silicone instead of PVC) or improve cooling — a larger cross-section is often cheaper than active cooling.

6 min readUpdated

+ 10–20% speling / clearance / SpielHimax. 60%
Figure: Bundling and clearance: the closer cables lie, the poorer the heat dissipation.

The temperature factor kT

Tables state ratings at 30 °C ambient. As ambient rises, less temperature difference remains to shed heat. For a PVC cable (70 °C conductor) kT is 0.87 at 40 °C, 0.71 at 50 °C and only 0.50 at 60 °C. A cable with 90 °C insulation retains far more at the same ambient.

The grouping factor kB

Cables touching each other heat each other. Two cables in a bundle already give kB = 0.80, five cables 0.60 and ten cables 0.50. Inside a carrier only simultaneously loaded power cables count; sensor cables hardly contribute. Layered routing with spacing gains a full factor step.

What if the result is too low?

There are four levers: larger cross-section, higher temperature class, better distribution (split the bundle) and active cooling. Compare total cost: one copper size up is usually cheaper than a fan that needs maintenance and can fail. A heat mat only helps against external radiation, not own loss heat.

Verify with a measurement

Verify your result with a thermocouple on the sheath of the hottest cable, in the middle of the bundle, during the heaviest cycle. If sheath temperature stays below the conductor limit minus 10 °C margin, you are fine. Log at least one full production cycle including start-up.

TableTemperature factor kT per insulation class
AmbientPVC 70 °CPUR/XLPE 90 °CSilicone 180 °C
30 °C1,001,001,00
40 °C0,870,910,97
50 °C0,710,820,94
60 °C0,500,710,91
80 °C0,410,84
120 °C0,65

Frequently asked questions

Do these factors also apply inside a cable carrier?
Yes, and more strictly: air exchange is limited in a closed carrier. Take one step more severe on kB and use separators so power cables do not touch.
May I ignore derating with a short duty cycle?
Partly. With a duty cycle under 25% and cycles shorter than the cable's thermal time constant you may use the RMS current, but always keep 10 °C margin.
Can you verify the cross-section for me?
Yes. Send current, cable length, ambient temperature, number of simultaneously loaded cables and the cable type; you receive advice on size, type and heat protection if needed.

Read next

Back to the knowledge base