Choose your delivery country
Ships today when ordered before 15:00 CETShips today when ordered before 15:00 CET
Wisman Group

Calculating

Calculating derating at high ambient temperature

Short answerMultiply the base current rating by the temperature factor kT and the grouping factor kB: I_allowed = I_base × kT × kB. If the required current exceeds that, choose a larger conductor size, a cable with a higher temperature class (silicone instead of PVC) or improve cooling — a larger cross-section is often cheaper than active cooling.

6 min readUpdated

The temperature factor kT

Tables state ratings at 30 °C ambient. As ambient rises, less temperature difference remains to shed heat. For a PVC cable (70 °C conductor) kT is 0.87 at 40 °C, 0.71 at 50 °C and only 0.50 at 60 °C. A cable with 90 °C insulation retains far more at the same ambient.

The grouping factor kB

Cables touching each other heat each other. Two cables in a bundle already give kB = 0.80, five cables 0.60 and ten cables 0.50. Inside a carrier only simultaneously loaded power cables count; sensor cables hardly contribute. Layered routing with spacing gains a full factor step.

What if the result is too low?

There are four levers: larger cross-section, higher temperature class, better distribution (split the bundle) and active cooling. Compare total cost: one copper size up is usually cheaper than a fan that needs maintenance and can fail. A heat mat only helps against external radiation, not own loss heat.

Verify with a measurement

Verify your result with a thermocouple on the sheath of the hottest cable, in the middle of the bundle, during the heaviest cycle. If sheath temperature stays below the conductor limit minus 10 °C margin, you are fine. Log at least one full production cycle including start-up.

Table — Temperature factor kT per insulation class
AmbientPVC 70 °CPUR/XLPE 90 °CSilicone 180 °C
30 °C1,001,001,00
40 °C0,870,910,97
50 °C0,710,820,94
60 °C0,500,710,91
80 °C—0,410,84
120 °C——0,65

Frequently asked questions

Do these factors also apply inside a cable carrier?
Yes, and more strictly: air exchange is limited in a closed carrier. Take one step more severe on kB and use separators so power cables do not touch.
May I ignore derating with a short duty cycle?
Partly. With a duty cycle under 25% and cycles shorter than the cable's thermal time constant you may use the RMS current, but always keep 10 °C margin.
Can you verify the cross-section for me?
Yes. Send current, cable length, ambient temperature, number of simultaneously loaded cables and the cable type; you receive advice on size, type and heat protection if needed.

Products from this article

Available from stock, with volume discounts from 10 pieces.

Read next

Back to the knowledge base